TO
CALCULATE
SINGLE
PHASE
THREE
PHASE
DIRECT
CURRENT
Kilowatts I x E x PF
1000
I x E x 1.732 x PF
1000
I x E
1000
KVA I x E
1000
I x E x 1.732
1000
-
Horsepower
(Output)
I x E x %EFF x PF
746
I x E x 1.732 x %EFF x PF
746
I x E x %EFF
746
Amperes when
horsepower is
known
HP x 746
E x %EFF x PF
HP x 746
1.732 x E x %EFF x PF
HP x 746
E x %EFF
Amperes when
Kilowatts is
known
KW x 1000
E x PF
KW x 1000
1.732 x E x PF
KW x 1000
E
Amperes when
KVA is known
KVA x 1000
E
KVA x 1000
1.732 x E
-
E = Volts %EFF = Percent Efficiency I = Amperes PF = Power Factor
REGULATION FOR TRANSFORMERS.
At unity P.F. and F.L. ( NL - FL ) E
NL x E
= R% x ( X% )2
200
TO CALCULATE VOLTAGE DROP ON FULL LOAD.
At 0.8 P.F. and F.L.=
R = Losses X = Reactance NL = No Load
E = Volts FL = Full Load PF = Power Factor